Hvac Component Start Up

HVAC (Heating, Ventilation and Airconditioning) component start-up procedures describe how to start the operation of each component. They specify the methods to be used and the checks that are needed. Start-ups and related measurements are carried out by the contractor. Commissioning provider assists the contractor in the beginning of each start-up process and reviews that no systematic errors are made.

HVAC Components

As an example, the following components or systems need to be started:

  • Dedicated outdoor air units, treated fresh air units and air handling units;
  • Variable Frequency Drivers (VFD);
  • Exhaust and supply fans;
  • Ductwork balancing;
  • Chillers;
  • Cooling towers;
  • Pumps;
  • Pipework balancing;
  • Variable Refrigerant Flow (VRF) system;
  • Heat pump system;
  • Precision air conditioning units;
  • Building management system (BMS).

Most of the start-ups also require measurements. The contractor must have sufficient measuring devices to carry on tests (Table below). Accuracy of each measuring device shall be good enough and the measurement range sufficient to the measured level. It is also important to have each measuring device calibrated less than one year ago. The contractor shall incorporate equipment type, accuracy, measurement range and calibration certificate of each measuring device as part of startup reports.

All measurement data shall be recorded using the template specified in the commissioning plan. After the start-up measurements of each equipment or subsystem, the contractor gives all reports for Cx provider, who provides a start-up review report to a client.

   
Object   
   
Measurement device   
   
Measurement   
   
Air flow rate   
   
Vane anemometer   
   
Velocity in AHU filter section or grille   
   
Hot wire anemometer   
   
Velocity inside duct   
   
Pitot tube and manometer   
   
Pressure difference in duct   
   
Capture hood & manometer   
   
Air flow rate of grille or diffuser   
   
Air velocity   
   
Hot wire anemometer   
   
Velocity of air   
   
Vane anemometer   
   
Velocity of air (>0.5 m/s)   
   
Ductwork leakage   
   
Duct leakage tester   
   
Static pressure inside ductwork   
   
Pressure of air   
   
Pressure manometer   
   
Differential pressure in ductwork or e.g.   
   
(Barometric) pressure meter   
   
Atmospheric pressure   
   
Pressure difference data logger   
   
Continuous pressure difference recording   
   
Pressure of water   
   
Hydronic manometer   
   
Differential pressure   
   
Pressure data logger   
   
Continuous pressure recording   
   
Water flow rate   
   
Hydronic manometer    
   
Pressure across control valve   
   
Digital flow rate meter   
   
Water flow rate   
   
Temperature   
   
Thermometer   
   
Liquid or air temperature   
   
Hot wire anemometer   
   
Air temperature (dry bulb)   
   
Surface temperature meter   
   
Surface temperature   
   
Infrared temperature meter   
   
Surface temperature   
   
Thermal imaging camera   
   
Surface temperature   
   
Sling psychrometer   
   
Wet/dry bulb temperature   
   
Temperature data logger   
   
Continuous temperature recording   
   
Humidity   
   
Hygrometer   
   
Absolute and relative humidity   
   
Sling psychrometer   
   
Dew point   
   
Relative humidity meter   
   
Relative humidity   
   
Indoor air quality   
   
Carbon dioxide meter (NDIR)   
   
CO 2-level of air   
   
Carbon monoxide meter (NDIR)   
   
CO-level of air   
   
Particulate meter (gravimetric, light-
   scattering or beta-attenuation)   
   
Particulate mass concentration and/or
   particulate count   
   
Photo-ionization detector (PID)   
   
fVoarrimoaulsd eVhOyCdse like TVOC and   
   
Electro-chemical sensor   
   
Various gases like SO 2, NO2, O3   
   
Andersson active air sampler withpetri dish   
   
Total Fungal and Bacterial Count   
   
Refrigeration   
   
Vacuum gauge   
   
Refrigerant system vacuum   
   
Refrigerant leak detector   
   
Refrigerant leakage   
   
Refrigeration manifold   
   
Pressure difference in pipe   
   
Filter leak testing   
   
Aerosol photometer and generator   
   
tCoo cnhdietciok nins sotfa ltlhatei oHnEPA filter as well as   
   
Sound   
   
Sound level meter   
   
Sound pressure levels in octave bands,   
   
Fan operation   
   
Tachometer   
   
RPM of rotating objectives   
   
Energy and power   
   
Plug-load meter   
   
Power consumption of device   
   
Clamp meter   
   
Voltage and current   
   
Electricity multi-meter   
   
Voltage, current, resistance   
HVAC COMMISSIONING GUIDEBOOK  - Maija Virta  ((M.Sc.Eng) is the Founder Director of the Santrupti engineers Pvt Ltd. She has over 30 years of experience in construction and HVAC-industry around the world)