The rate at which air is exchanged (in the premises) represents another method of measuring ventilation capacity & effectiveness. Air exchange rate is typically expressed in Air Changes per Hour – “ACH”. Air changes per hour can be estimated by determining the total air supplied to, and removed from, the premises “total air exchange” or the outdoor (fresh) air supplied to, and removed from, the premises “outdoor air exchange”.
Esta tabla proporciona cambios de aire sugeridos por hora (ACH) en condiciones normales según una buena experiencia.
Salas de reuniones |
4 – 8 |
salones de peluqueria |
10 – 15 |
Panaderías |
20 – 30 |
Hospitales – esterilización |
15 – 25 |
Bancos/sociedades de construcción |
4 – 8 |
Hospitales – salas |
6 – 8 |
Baños |
6 – 10 |
Cocinas – domésticas |
15 – 20 |
Dormitorios |
2 – 4 |
Cocinas# - comercial |
30 mínimo |
Salas de billar* |
6 – 8 |
Laboratorios |
6 – 15 |
Salas de calderas |
15 – 30 |
Lavanderías/Lavanderías |
10 – 15 |
Cafés y cafeterías |
10 – 12 |
Lavanderías |
10 – 30 |
cantinas |
8 – 12 |
Lavabos |
6 – 15 |
bodegas |
3 – 10 |
Salas de conferencias |
5 – 8 |
Vestuarios Zona principal |
6 – 10 |
bibliotecas |
3 – 5 |
Vestuarios Zona de duchas |
15 – 20 |
Salas |
3 – 6 |
Iglesias |
1 – 3 |
Casas de hongos |
6 – 10 |
Cines y teatros* |
10 – 15 |
Oficinas |
6 – 10 |
Salas Club |
12 mínimo |
Talleres de pintura (no celulosa) |
10 – 20 |
Salas de compresores |
10 – 20 |
Cuartos oscuros de fotografía y rayos X |
10 – 15 |
Salas de conferencias |
8 – 12 |
bares de tabernas |
12 mínimo |
Lácteos |
8 – 10 |
Salas de control de grabación |
15 – 25 |
Salones de baile |
12 mínimo |
Estudios de grabación |
10 – 12 |
Cirugías dentales |
12 – 15 |
Restaurantes |
8 – 12 |
Trabajos de tinte |
20 – 30 |
aulas |
5 – 7 |
Talleres de galvanoplastia |
10 – 12 |
Tiendas y supermercados |
8 – 15 |
Salas de máquinas |
15 – 30 |
Baños de ducha |
15 – 20 |
Halls de entrada y pasillos |
3 – 5 |
Tiendas y almacenes |
3 – 6 |
Fábricas y talleres |
8 – 10 |
Pistas de squash |
4 mínimo |
Fundiciones |
15 – 30 |
Baños de natación |
10 – 15 |
garajes |
6 – 8 |
Baños |
6 – 10 |
Casas de vidrio |
25 – 60 |
Cuartos de servicio |
15 – 20 |
Gimnasios |
6 mínimo |
Talleres de soldadura |
15 – 30 |
*Aumente en un 50% cuando se fuma mucho o si la habitación está bajo tierra.
#Algunas cocinas comerciales pueden requerir tasas de ventilación más altas, según el equipo de cocina utilizado.
FREQUENTLY ASKED QUESTIONS
To calculate the total air exchange rate, you need to determine the total air supplied to and removed from the premises. This can be done by summing up the airflow rates of all supply and exhaust fans, as well as any natural ventilation sources. The total air exchange rate is then divided by the volume of the premises to obtain the air changes per hour (ACH). For example, if the total air supplied is 10,000 CFM and the premises has a volume of 50,000 cubic feet, the total air exchange rate would be 10,000 CFM / 50,000 cu.ft = 0.2 air changes per hour.
Total air exchange refers to the total amount of air supplied to and removed from a premises, including recirculated air. Outdoor air exchange, on the other hand, only considers the fresh air brought in from outside and exhausted to the outdoors. While total air exchange provides a broader picture of ventilation, outdoor air exchange is a more direct indicator of the premises’ ability to remove pollutants and provide fresh air to occupants.
The required air changes per hour (ACH) for a specific space depends on various factors, including occupancy, activity level, and desired indoor air quality. The table provided in the blog post offers suggested ACH values for different spaces under normal conditions. However, it’s essential to consult relevant standards, such as ASHRAE 62.1, and consider specific requirements for your project. Additionally, you may need to perform calculations based on the space’s volume, occupancy, and ventilation system design.
Air changes per hour (ACH) can be used as a rough estimate for ventilation system sizing, but it’s not a direct correlation. ACH provides a general indication of the required ventilation rate, but it doesn’t account for factors like duct losses, fan efficiency, and heat gain/loss. To accurately size a ventilation system, you should perform detailed calculations considering these factors, as well as the specific requirements of your project.
Air changes per hour (ACH) has a significant impact on energy consumption in HVAC systems. Higher ACH values require more energy to operate fans, heat, and cool the air. Conversely, lower ACH values can lead to reduced energy consumption. However, it’s essential to strike a balance between ACH and energy efficiency, as inadequate ventilation can lead to poor indoor air quality and occupant discomfort. Optimizing ACH based on the specific needs of your project can help minimize energy consumption while maintaining a healthy and comfortable indoor environment.