The expansion valve regulates the amount of compressed liquid refrigerant moving into the evaporator. It removes pressure from the liquid refrigerant to allow expansion or change of state from a liquid to a gas in the evaporator.

Thermostatic Expansion Valve
There are two types of expansion valves commonly used on air conditioning systems:
- Internally-equalized valve
It receives warm high-pressure liquid refrigerant and leaves the expansion valve quite cold. Keep in mind that the expansion valve does not lower heat. It only decreases the pressure. Thus, the heat molecules can spread out more as it is moving out of the valve and becomes very cold.
- Externally-equalized valve
Operation of the externally-equalized valve is the same as the internal type except that evaporator pressure is fed against the underside of the valve diaphragm from the tailpipe of the evaporator by an equalizer line. This balances the temperature of the expansion valve when it is doing the phase conversion.
In order to properly select Expansion Valves, the following items should be considered:
- Required valve capacity should be based on the actual system operating conditions rather than the normal valve capacity rating.
- When there exists an appreciable pressure drop between the valve outlet and the evaporator outlet, i.e., above 0.02 MPa (0.2 kgf/cm2), or when a pressure drop type of refrigerant distributor is used at the evaporator inlet, the valve should have the external equalizer feature for best performance. Otherwise, it will increase a static superheat (valve opening temp.), restricting the refrigerant flow and causing the reduction of system capacity. As for R134a, 0.01 MPa {0.1kgf/cm2} pressure drop will increase the static superheat approximately 1°C.
- Internally equalized valve may be used with the evaporator which has a negligible pressure drop, i.e., below 0.02 MPa (0.2 kgf/cm2).
EQUALIZER
Un égaliseur interne ou externe doit être sélectionné en fonction de la chute de pression entre la sortie de la vanne et la sortie de l'évaporateur. L'égaliseur interne augmente la surchauffe dans le système de réfrigération dont l'évaporateur présente une certaine chute de pression, et l'augmentation de la surchauffe diminue la surface effective de l'évaporateur.
Sélectionnez un égaliseur interne ou externe en fonction du réfrigérant, de la chute de pression et de la température d'évaporation. Le tableau guide pour l'égaliseur indique la différence de pression du réfrigérant correspondant à une température de 1 °C. Les vannes d'égalisation externes doivent être utilisées lorsque la chute de pression dépasse la valeur de différence de pression indiquée dans le tableau.

RÉGLAGE DE LA SURCHAUFFE
Le régulateur de surchauffe du détendeur ajuste la surchauffe par laquelle la vanne commence à s'ouvrir à partir de l'état complètement fermé, et cette surchauffe est appelée surchauffe statique.
- SSH : Surchauffe statique
- O.S.H.: Operating Superheat (Superheat necessary for valve and refrigeration system operation)
- S.H.C.: Superheat Change (Superheat which keeps the valve opening at the optimum balance point for refrigeration systems)
SSH = SST − SHC
Pour modifier le réglage, retirez le capuchon d'étanchéité et tournez la broche de réglage. Tourner la broche dans le sens des aiguilles d'une montre pour comprimer le ressort diminue le débit et augmente la surchauffe et tourner la broche dans le sens inverse des aiguilles d'une montre pour desserrer le ressort augmente le débit et diminue la surchauffe.
CHARGE & MOP (MAXIMUM OPERATING PRESSURE)
Charge G
La charge de gaz utilisée généralement sur la climatisation limite la pression, mais perd le contrôle si le corps de la vanne devient plus froid que l'ampoule de détection. Une vanne chargée en gaz doit être installée dans un endroit où le corps de la vanne peut être plus chaud que l'ampoule pour éviter la condensation de la charge dans la tête motrice.
L–Charge
Liquid charge provides accurate control when valve body becomes colder than sensing bulb; hence a liquid charged valve may be installed in any location regardless of temperature. The charge, however, does not provide maximum operating pressure (pressure limiting) for motor overload protection.
C&CL&CY–Frais
Cross charge and Cross Low Temp. charge used generally on low temperature range application will not lose control even if valve body becomes colder than sensing bulb. A cross charged valve may be installed in any location regardless of temperature. Cross charge (C) for normal refrigeration (higher than − 40°C temp. range) and Cross Low Temp. charge (CL and CY) for low temp. refrigeration (CY… − 70 to − 40°C with R22 for Type ATX valves).
S&SA&SL–Frais
The charge provides accurate control even if valve body becomes colder than sensing bulb and further it provides MOP (pressure limiting) for motor overload protection. S–charged valve may be installed in any location regardless of temperature.
COMMANDE de détendeurs
- Pression normale et pression maximale
- Température normale et température minimale
- Demande détaillée
- Réfrigérant
- Emplacement de la vanne
- Capacity (Condensing & Evaporating Temperature)
- Longueur du tube capillaire
- Évaporateur externe ou interne
- Chute de pression à l'évaporateur
- MOP (Maximum Operating Pressure)
- Système de compresseur à deux étages ou non