Plenum Box Size Calculator

Plenum Box Size Calculator

Plenum Box Size Calculator

Sizes a supply or return plenum box (cross-section, width/height, length and depth) from airflow and target face velocity for AHU/FCU duct systems.

HVAC Ductwork · Preliminary Sizing · ACCA Manual D basis
Inputs
Units & application
Airflow & velocity
CFM
FPM
Design velocity auto-suggests when you change plenum service; edit freely.
Sizing method
in
Length & depth
in
ACCA Manual D: length preferred 1–3× width (2× typical); minimum 18 in past the last trunk takeoff.
Advanced inputs

in
Depth ≈ 2.5 × d gives entering air room to straighten before the first takeoff. Leave 0 to skip.
Result
Recommended plenum size (W × H × L)
Awaiting input

Required area
Actual velocity
Aspect ratio W:H
Recommended length
Depth (fan check)
Velocity range target

Recommended next engineering action
Enter airflow and velocity, then press Calculate.
Formulas & Variables

A = Q / V

W × H = A (solve W from fixed H, or W = √(A × ratio), H = W / ratio)

L = multiplier × W (≥ minimum length past last takeoff); D ≈ 2.5 × d

SymbolMeaningUnit basis (Imperial)Unit basis (Metric)
QDesign airflowCFM (ft³/min)m³/h → converted to m³/s
VTarget face velocity in plenumFPM (ft/min)m/s
ARequired cross-sectional areaft² (×144 for in²)
W, HPlenum width and heightinmm
LPlenum lengthinmm
DPlenum depth (entrance settling length)inmm
dBlower wheel/outlet diameterinmm
Step 1. Convert airflow and velocity to consistent units.
Step 2. Compute required cross-section A = Q / V.
Step 3. Solve W and H (fixed height or fixed W:H ratio, target 2–3:1).
Step 4. Set length L = 1–3×W (2×W preferred), ≥ minimum length past last takeoff.
Step 5. Optionally check depth D ≈ 2.5×d against available install space.
Assumptions & Limits

Design conditions / defaults

  • Rectangular sheet-metal plenum, straight, no internal obstructions.
  • Uniform velocity profile across the cross-section.
  • Default velocities: residential supply 500–700 FPM, residential return 300–400 FPM, commercial/AHU supply 700–900 FPM, commercial return 500–800 FPM.
  • Length: 1–3× width (2× preferred); minimum 18 in past the last takeoff (ACCA Manual D).

Included effects

  • Airflow-velocity relationship for cross-section sizing.
  • Aspect ratio guidance (target ≤ 4:1) for airflow stability.
  • Optional blower-diameter based depth check.

Excluded effects

  • Static pressure drop, fitting losses, and turning-vane effects.
  • Acoustic/noise attenuation and insulation thickness.
  • Number, spacing, or layout of branch takeoffs and diffusers.
  • Sheet-metal gauge, reinforcement, and structural support.

Valid input range / intended use

  • Preliminary sizing for residential and light-commercial AHU/FCU supply and return plenums.
  • Airflow > 0 and velocity > 0; not intended for high-pressure ducted systems or cleanroom/lab exhaust plenums.
Engineering Notes
  • Never neck the plenum down below the equipment opening — the plenum decelerates air, it should not restrict it.
  • Keep the width 2–3× the connecting supply trunk width; use the pivot point sizing method for slot/linear diffusers if a manufacturer nomogram is available.
  • An aspect ratio (W:H) beyond 4:1 tends to create dead zones and uneven takeoff distribution — consider splitting into two plenums instead.
  • If the plenum feeds multiple branch takeoffs, keep 150–200 mm (6–8 in) spacing between collars and avoid placing outlets directly opposite the inlet.

Reference method

Based on ACCA Manual D box-plenum sizing guidance and standard AHU supply/return velocity practice (typical AHU design velocity 700–900 FPM).

Revision: v1.0 · August 2026.

Disclaimer: This tool provides preliminary, order-of-magnitude sizing for design development only. It does not account for static pressure losses, acoustics, structural support, or code-specific requirements. Final plenum dimensions must be verified and stamped by a licensed mechanical/HVAC engineer in accordance with applicable codes (e.g., ACCA Manual D, SMACNA, ASHRAE) and manufacturer data.