Relief Valve Calculations And Equations

Pressure relief devices (PRD’s) are widely and effectively used to protect process equipment such as piping systems, pressure vessels, distillation columns and other equipment from pressures exceeding the design-pressure rating by more than a fixed predetermined amount. The aim of pressure relief valves is to prevent damage to equipment, prevent injury to personnel and to avoid potential risks to the environment.

Pressure relief valve

Relief Valve Vent Line Maximum Length

The equation for the maximum length of a relief vent line is:

$$ L=\frac{9 \times P_1^2 \times D^5}{C^2}=\frac{9 \times P_2^2 \times D^5}{16 \times C^2} $$

P1 = 0.25 × [(PRESSURE SETTING × 1.1) + 14.7]

P2 = [(PRESSURE SETTING × 1.1) + 14.7]

L = Maximum Length of Relief Vent Line (Feet)

D = Inside Diameter of Pipe (Inches)

C = Minimum Discharge of Air (Lbs./Min.)

The first term in the equation, \(\frac{9 \times P_1^2 \times D^5}{C^2}\), represents the pressure drop in the relief vent line due to friction. The second term in the equation, \(\frac{9 \times P_2^2 \times D^5}{16 \times C^2}\), represents the pressure drop in the relief vent line due to the expansion of the gas as it flows through the pipe.

The equation is set equal to zero because it represents the maximum length of the relief vent line for which the pressure drop will not exceed the set pressure of the relief valve. If the length of the relief vent line is greater than the maximum length, then the pressure drop in the line will exceed the set pressure of the relief valve, and the valve will not open properly.

The equation can be used to design relief vent lines for a variety of applications, such as pressure vessels, boilers, and compressors. It is important to note that the equation is only valid for single-phase gas flow. If the fluid flowing through the relief vent line is a two-phase mixture of gas and liquid, then the equation will need to be modified.

Here is an example of how to use the equation to calculate the maximum length of a relief vent line:

The first step is to calculate the back pressure at the relief valve outlet:

P_1 = 0.25 * [(150 psig + 14.7 psia) * 1.1] + 14.7 psia = 42.6 psia

The next step is to calculate the inside diameter of the relief vent pipe:

D = 1.5 inches - 0.133 inches (wall thickness of Schedule 40 steel pipe) = 1.367 inches

Finally, we can substitute all of the known values into the equation to calculate the maximum length of the relief vent line:

L = 9 * 42.6^2 * 1.367^5 / 100^2 = 272 feet

Therefore, the maximum length of the relief vent line is 272 feet.


Relief Valve Sizing

Liquid System Relief Valves and Spring Style Relief Valves:

$$ A=\frac{G P M \times \sqrt{G}}{28.14 \times K_B \times K_V \times \sqrt{\Delta P}} $$

Liquid System Relief Valves and Pilot Operated Relief Valves:

$$ A=\frac{G P M \times \sqrt{G}}{36.81 \times K_V \times \sqrt{\Delta P}} $$

Steam System Relief Valves:

$$ A=\frac{W}{51.5 \times K \times P \times K_{S H} \times K_N \times K_B} $$

Gas and Vapor System Relief Valves (Lb./Hr.):

$$ A=\frac{W \times \sqrt{T Z}}{C \times K \times P \times K_B \times \sqrt{M}} $$

Gas and Vapor System Relief Valves (SCFM):

$$ A=\frac{S C F M \times \sqrt{T G Z}}{1.175 \times C \times K \times P \times K_B} $$

Definitions:

  • A: Minimum required effective relief valve discharge area (square inches)
  • GPM: Required relieving capacity at flow conditions (gallons per minute)
  • W: Required relieving capacity at flow conditions (pounds per hour)
  • SCFM: Required relieving capacity at flow conditions (standard cubic feet per minute)
  • G: Specific gravity of liquid, gas, or vapor at flow conditions (water = 1.0 for most HVAC applications; air = 1.0)
  • C: Coefficient determined from the expression of the ratio of specific heats (C = 315 if value is unknown)
  • K: Effective coefficient of discharge (K = 0.975)
  • KB: Capacity correction factor due to back pressure (KB = 1.0 for atmospheric discharge systems)
  • KV: Flow correction factor due to viscosity (KV = 0.9 to 1.0 for most HVAC applications with water)
  • KN: Capacity correction factor for dry saturated steam at set pressures above 1500 psia and up to 3200 psia (KN = 1.0 for most HVAC applications)
  • KSH: Capacity correction factor due to the degree of superheat (KSH = 1.0 for saturated steam)
  • Z: Compressibility factor (Z = 1.0 if value is unknown)
  • P: Relieving pressure (psia) (P = set pressure (psig) + overpressure (10% psig) + atmospheric pressure (14.7 psia))
  • ∆P: Differential pressure (psig) (∆P = set pressure (psig) + overpressure (10% psig) − back pressure (psig))
  • T: Absolute temperature (°R = °F + 460)
  • M: Molecular weight of the gas or vapor

Relief Valve Sizing Notes:

  • When multiple relief valves are used, one valve shall be set at or below the maximum allowable working pressure, and the remaining valves may be set up to 5 percent over the maximum allowable working pressure.
  • When sizing multiple relief valves, the total area required is calculated on an overpressure of 16 percent or 4 Psi, whichever is greater.
  • For superheated steam, the correction factor values listed below may be used:

Superheat Calculator


Selected Superheat: 0 °F

Correction Factor: 0.97

Superheat Value
Correction Factor
Superheat up to 400 °F
0.97 (Range 0.979–0.998)
Superheat up to 450 °F
0.95 (Range 0.957–0.977)
Superheat up to 500 °F
0.93 (Range 0.930–0.968)
Superheat up to 550 °F
0.90 (Range 0.905–0.974)
Superheat up to 600 °F
0.88 (Range 0.882–0.993)
Superheat up to 650 °F
0.86 (Range 0.861–0.988)
Superheat up to 700 °F
0.84 (Range 0.841–0.963)
Superheat up to 750 °F
0.82 (Range 0.823–0.903)
Superheat up to 800 °F
0.80 (Range 0.805–0.863)
Superheat up to 850 °F
0.78 (Range 0.786–0.836)
Superheat up to 900 °F
0.75 (Range 0.753–0.813)
Superheat up to 950 °F
0.72 (Range 0.726–0.792)
Superheat up to 1000 °F
0.70 (Range 0.704–0.774)
Relief valve design correction factors

Material Properties


Properties:

Molecular Weight:

Ratio of Specific Heats:

Coefficient C:

Specific Gravity:

You may use table instead of calculator

GAS OR VAPOR
MOLECULAR WEIGHT
RATIO OF SPECIFIC HEATS
COEFFICIENT C
SPECIFIC GRAVITY
Acetylene
26.04
1.25
342
0.899
Air
28.97
1.40
356
1.000
Ammonia (R-717)
17.03
1.30
347
0.588
Argon
39.94
1.66
377
1.379
Benzene
78.11
1.12
329
2.696
N-Butane
58.12
1.18
335
2.006
Iso-Butane
58.12
1.19
336
2.006
Carbon Dioxide
44.01
1.29
346
1.519
Carbon Disulphide
76.13
1.21
338
2.628
Carbon Monoxide
28.01
1.40
356
0.967
Chlorine
70.90
1.35
352
2.447
Cyclohexane
84.16
1.08
325
2.905
Ethane
30.07
1.19
336
1.038
Ethyl Alcohol
46.07
1.13
330
1.590
Ethyl Chloride
64.52
1.19
336
2.227
Ethylene
28.03
1.24
341
0.968
Helium
4.02
1.66
377
0.139
N-Heptane
100.20
1.05
321
3.459
Hexane
86.17
1.06
322
2.974
Hydrochloric Acid
36.47
1.41
357
1.259
Hydrogen
2.02
1.41
357
0.070
Hydrogen Chloride
36.47
1.41
357
1.259
Hydrogen Sulphide
34.08
1.32
349
1.176
Methane
16.04
1.31
348
0.554
Methyl Alcohol
32.04
1.20
337
1.106
Methyl Butane
72.15
1.08
325
2.491
Methyl Chloride
50.49
1.20
337
1.743
Natural Gas
19.00
1.27
344
0.656
Nitric Oxide
30.00
1.40
356
1.036
Nitrogen
28.02
1.40
356
0.967
Nitrous Oxide
44.02
1.31
348
1.520
N-Octane
114.22
1.05
321
3.943
Oxygen
32.00
1.40
356
1.105
N-Pentane
72.15
1.08
325
2.491
Iso-Pentane
72.15
1.08
325
2.491
Propane
44.09
1.13
330
1.522
R-11
137.37
1.14
331
4.742
R-12
120.92
1.14
331
4.174
R-22
86.48
1.18
335
2.985
R-114
170.93
1.09
326
5.900
R-123
152.93
1.10
327
5.279
R-134a
102.03
1.20
337
3.522
Sulfur Dioxide
64.04
1.27
344
2.211
Toluene
92.13
1.09
326
3.180
Gas and Vapor Properties for relief valve calculation