Expansion tanks are a necessary part of all closed hydronic systems to control both minimum and maximum pressure throughout the system. Expansion tanks are provided in closed hydronic systems to (1) accept changes in system water volume as water density changes with temperature to keep system pressures below equipment and piping system component pressure rating limits. Also, (2) maintain a positive gauge pressure in all parts of the system to prevent air from leaking into the system. (3) Maintain sufficient pressures in all parts of the system to prevent boiling, including cavitation at control valves and similar constrictions. (4) Maintain net positive suction head required (NPSHR) at the suction of pumps.
The latter two points generally apply only to high temperature (greater than approximately 210°F [99°C]) hot water systems. For most HVAC applications, only the first two points need to be considered.
Tank Styles
There are four basic styles of expansion tanks:
Vented or open steel tanks
Since they are vented, open tanks must be located at the highest point of the system. Water temperature cannot be above 212°F (100°C), and the open air/water contact results in a constant migration of air into the system, causing corrosion. Accordingly, this design is almost never used anymore.
Closed steel tanks
Also called plain steel tanks or compression tanks by some manufacturers.
This is the same tank style as the vented tank, but with the vent capped. This allows the tank to be located anywhere in the system and work with higher temperatures. But they still have the air/water contact that allows for corrosion, and sometimes a gradual loss of air from the tank as it is absorbed into the water.
Unless precharged to the minimum operating pressure prior to connection to the system, this style of tank also must be larger than precharged tanks. Accordingly, this design is also almost never used anymore.
Diaphragm tanks
This was the first design of a compression tank that included an air/water barrier (a flexible membrane, to eliminate air migration) and that was designed to be precharged (to reduce tank size). The flexible diaphragm typically is attached to the side of the tank near the middle and is not field replaceable; if the diaphragm ruptures, the tank must be replaced.
Bladder tanks
Bladder tanks use a balloon-like bladder to accept the expanded water. Bladders are often sized for the entire tank volume, called a “full acceptance” bladder, to avoid damage to the bladder in case they become waterlogged. Bladders are gener ally field replaceable. This is now the most common type of large commercial expansion tank.
Sizing Formulas
The general formula for tank sizing, Equation 1 (with variable names adjusted to match those used in this article), from basic principles assuming perfect gas laws:
$$V_t = \frac{V_s(E_w – E_p)}{(P_s T_c / P_i T_s) – (P_s T_h / P_{max} T_s) – E_{wt}[1 – (P_s T_c / P_{max} T_s)] + E_t} – 0.02 V_s$$Where
Vt = tank total volume
Vs = system volume
Ps = starting pressure when water first starts to enter the tank, absolute
Pi = initial (precharge) pressure, absolute
Pmax = maximum pressure, absolute
Ew = unit expansion ratio of the water in the system due to temperature rise = (νh/νc-1)
vh = the specific volume of water at the maximum temperature, Th.
vc = the specific volume of water at the minimum temperature, Tc .
Ep = unit expansion ratio of the piping and other system components in the system due to temperature rise = 3α(Th-Tc )
α = coefficient of expansion of piping and other system components, per degree
Th = maximum average water temperature in the system, degrees absolute
Tc = minimum average water temperature in the system, degrees absolute
Ts = starting air temperature in the tank prior to fill, degrees absolute
Ewt = unit expansion ratio of water in the tank due to temperature rise
Et = unit expansion ratio of the expansion tank due to temperature rise
The last term (0.02 Vs ) accounts for additional air from desorption from dissolved air in the water. This equation can be simplified to Equation below by ignoring small terms and assuming tank temperature stays close to the initial fill temperature (typically a good assumption, assuming no insulation on the tank or piping to it, which is a common, and recommended, practice):
$$V_t = \frac{V_s\left(\frac{v_h}{v_c} – 1 – 3\alpha(T_h – T_c)\right)}{\frac{P_s}{P_i} – \frac{P_s}{P_{max}}}$$This equation includes the credit for the expansion of the piping system. This term is also relatively small and the expansion coefficients are hard to determine given the various materials in the system, but it is included in Equation above since it is included in the ASHRAE Handbook sizing equations. This term is also included in some, but not most, expansion tank manufacturers’ selection software. Most manufacturers conservatively ignore this term since it is small and no larger than the terms already ignored in the above Equation. Ignoring this term results in Equation below:
$$V_t = \frac{(((v_h/v_c) – 1) V_s)}{(P_s/P_i) – (P_s/P_{max})}$$The numerator is the volume of the expanded water, Ve , as it warms from minimum to maximum temperatures, so the equation can be written:
$$V_t = \frac{V_e}{\frac{P_s}{P_i} – \frac{P_s}{P_{max}}}$$Where:
$$V_e = (v_h/v_c – 1) V_s$$The equation can be further simplified based on the style of tank used.
Vented tank
For vented tanks, the pressures are all the same and the dominator limits to 1, so the tank size is simply the volume of expanded water:
$$V_t = V_e$$Closed Tank (no precharge)
For unvented plain steel tanks, the starting pressure is typically atmospheric pressure with the tank empty (no precharge). The tank is then connected to the makeup water, which pressurizes the tank to the fill pressure by displacing air in the system, essentially wasting part of the tank volume. So the sizing equation is:
$$V_l = \frac{V_e}{\frac{P_a}{P_i} – \frac{P_a}{P_{max}}}$$Where, Pa = atmospheric pressure
Precharged Tank
For any tank that is precharged to the required initial pressure, including properly charged diaphragm and bladder tanks, but also including closed plain steel tanks if precharged, Ps is equal to Pi so the sizing equation reduces to:
$$V_t = \frac{V_e}{1 – \frac{P_i}{P_{max}}}$$Note that this equation only applies when the tank is precharged to the required Pi . Tanks are factory charged to a standard precharge of 12 psig (83 kPag).
Closed Tank
For higher desired precharge pressures, either a special order can be made from the factory or the contractor must increase the pressure with compressed air or a hand pump. But it is not uncommon for this to be overlooked. This oversight can be compensated for by sizing the tank using Equation below (assuming atmospheric pressure at sea level):
$$V_t = \frac{V_e}{\frac{26.7}{P_i} – \frac{26.7}{P_{max}}}$$(12 psig/26.7 psia [83 kPag/184 kPaa] precharge). This will increase the tank size vs. a properly precharged tank.
ASME Boiler and Pressure Vessel Code-2015, Section VI
ASME Boiler and Pressure Vessel Code-2015, Section VI, includes sizing equations (as do the UMC and IMC, which extract the equations verbatim), as shown in Equation below, with variables revised to match those used in this article:
$$V_t = \frac{V_s(0.00041T_h – 0.0466)}{\frac{P_a}{P_i} – \frac{P_a}{P_{max}}}$$Comparing the denominator of this Equation to Equation for Closed Tank (no precharge), this formula is clearly for sizing a nonprecharged tank; it will overestimate the size of a precharged tank. The numerator is a curve fit of Ve ; it assumes a minimum temperature of 65°F (18°C) and is only accurate in the range of about 170°F to 230°F (77°C to 110°C) average operating temperature. Therefore, this equation cannot be used for very high temperature hot water (e.g. 350°F [177°C]), closed-circuit condenser water, or chilled water systems.
Author: Steven T. Taylor, PE
FREQUENTLY ASKED QUESTIONS
Undersizing an expansion tank can lead to several consequences, including increased system pressure, reduced system efficiency, and potential equipment damage. Insufficient tank capacity can cause the system to exceed the pressure rating of equipment and piping components, leading to premature failure or even catastrophic failure. Additionally, undersizing can result in inadequate pressure maintenance, allowing air to enter the system and causing corrosion, erosion, and other issues.
To determine the required expansion tank size, you need to calculate the total volume of the system, including the volume of water in the pipes, radiators, and other components. You should also consider the maximum expected temperature change in the system, as well as the pressure rating of the equipment and piping components. Using formulas such as the one provided in the ASHRAE Handbook or other industry resources, you can calculate the required tank size based on these factors. It’s essential to consult with a qualified engineer or technician to ensure accurate calculations and proper tank sizing.
Open expansion tanks are vented to the atmosphere and are typically used in open systems where the tank is not pressurized. Closed expansion tanks, on the other hand, are pressurized and used in closed systems where the tank is subjected to system pressure. Closed tanks are more common in modern hydronic systems due to their ability to maintain a positive pressure and prevent air from entering the system. Open tanks are often used in older systems or in applications where the system pressure is relatively low. The choice between open and closed tanks depends on the specific system requirements and design.
While standard formulas can provide a good starting point for calculating expansion tank size, there are other factors to consider, such as system complexity, piping layout, and equipment specifications. For example, systems with multiple loops or zones may require larger tanks to accommodate the additional volume changes. Additionally, the type of fluid used in the system, such as water or glycol, can affect the tank sizing calculation. It’s essential to consider these factors and consult with industry resources or a qualified engineer to ensure accurate tank sizing.
Regular inspection and maintenance of the expansion tank are crucial to ensure optimal system performance and prevent potential issues. It’s recommended to inspect the tank at least annually, checking for signs of corrosion, damage, or leakage. Additionally, the tank should be drained and cleaned periodically to remove sediment and debris that can affect its performance. The frequency of maintenance may vary depending on the system design, operating conditions, and local regulations. Consult with a qualified technician or the tank manufacturer’s guidelines for specific maintenance recommendations.