Constant Air Volume (CAV) Systems

HVAC air systems can be either centralized or decentralized. Centralized air systems receive their cooling and heating energy from a remote central plant. Decentralized HVAC air systems contain the central heating and cooling plant equipment within the air system itself. HVAC air systems can also be constant air volume (CAV) or variable air volume (VAV). CAV systems deliver constant supply airflow at a variable temperature. VAV systems deliver variable supply airflow at a constant temperature. CAV and VAV air systems can be further subdivided into systems that condition a single temperature zone and systems that condition multiple temperature zones.

HVAC-CAV-System

Whether the HVAC air systems are centralized or decentralized, CAV or VAV, serve a single zone or multiple zones, the choices for heating and cooling coils within the units are the same. Generally, the heating coil in centralized HVAC air systems will be hot water, steam, or electric, and the cooling coil will be chilled water. The heating coil in decentralized HVAC systems will be electric, direct or indirect gas-fired or (reverse cycle) direct expansion (DX) refrigerant (for heat pumps only); the cooling coil will be DX refrigerant.

Einzelzone

A single-zone CAV system consists of an air handling unit that delivers constant supply airflow (Fig. 1). The heating and/or cooling capacity of the unit is modulated by varying the temperature of the supply airflow to meet the needs of a single thermostat mounted in one of the spaces served by the unit.

Abbildung 1: Einzonen-System mit konstantem Luftvolumen

Einzonen-CAV-Systeme können mehrere Räume bedienen; Daher ist es wichtig sicherzustellen, dass alle von einem Einzonen-CAV-System versorgten Räume ähnliche HVAC-Lasteigenschaften aufweisen.


Heizen und Lüften

Heating and ventilating (H&V) systems are used to serve spaces that require heating only and also require outdoor air ventilation for occupant ventilation or exhaust air makeup. H&V units are often configured to deliver 100% outdoor air. However, they may have return air capabilities if the outdoor airflow is less than the supply airflow that is required to provide effective heating of the spaces served during the winter. If the units heat the spaces they serve during unoccupied periods when the exhaust systems are off and the outdoor air dampers are shut, H&V units may also be equipped with return air capabilities. H&V units normally recirculate 100% of the air during the unoccupied mode of operation.

During the summer it is common for H&:V units to position their outdoor and return air dampers to deliver 100% outdoor air to the spaces served in order to maintain the space temperature at 5 to 10°F higher than the outdoor temperature. If the H&:V units have return air capabilities, provisions must be made within the spaces served to either relieve or exhaust the excess outdoor air that is introduced during the summertime mode of operation.

Temperature control for H&:V systems is the same as for the single-zone CAV system described earlier, except the space thermostat will control the heating capacity of the H&V unit only. Some common examples of spaces requiring H&V systems are gymnasiums, locker rooms, and kitchens:


Mehrere Zonen

CAV-Systeme eignen sich nicht gut für die Bereitstellung mehrerer Zonen zur Temperaturregelung, da die Versorgung mehrerer Zonen mit CAV-Systemen höhere Energiekosten und in einigen Fällen höhere Anschaffungskosten verursacht als die normalerweise verfügbaren VAV-Optionen. Durch den Einsatz von Nacherwärmungs-, Doppelkanal- und Mehrzonenkonfigurationen können CAV-Systeme jedoch für bestimmte Anwendungen, insbesondere bei Renovierungen bestehender Systeme, mehrere Temperaturzonen bedienen.


Aufwärmen

A CAV reheat system consists of a CAV unit whose supply air ductwork branches out to serve multiple zones within the area served by the unit (Fig. 2). A reheat coil is mounted within the branch duct to each zone. Typically, the discharge air temperature from the CAV unit is maintained at approximately 55°F so that it can meet the cooling needs of the temperature zones, if required. A heating-only thermostat located in each zone controls the heating output of its associated zone reheat coil. This coil reheats the supply air from the CAV unit as required to maintain the setpoint of the zone thermostat. If no heating is required in the zone, the heating coil will be shut off. The zone reheat coil needs to be sized not only to meet the building envelope heat losses for the zone but also to raise the supply airflow from the discharge air temperature (typically 55°F) to the zone cooling setpoint (typically 75°F).

Abbildung 2: Nacherwärmungssystem mit konstantem Luftvolumen

CAV reheat systems are not energy efficient because simultaneous cooling (at the CAV unit) and heating (at the reheat coil) of the supply airflow occu.rs. Care must be taken when designing CAV reheat systems because the 2018 International Energy Conservation Code, Section 503.4.5, requires the supply airflow to be reduced to at least 30% of the maximum supply airflow to each zone before reheating can occur. One exception to this rule is for .zones that have special humidity control requirements.


Doppelkanal

A dual-duct CAV system includes two separate supply air ducts, one hot duct and one cold duct, connected to a specially configured CAV air handling unit (Fig. 3). The supply airflow is divided within the unit downstream of the supply fan into what are called the hot deck and cold deck. A heating coil is installed within the unit in the hot deck and a cooling coil is installed within the unit in the cold deck. A portion of the supply airflow is blown through the hot deck and disclw:ged through the main hot duct connected to the unit. The remaining supply airflow is blown through the cold deck. and discharged through the main cold duct connected to the unit. Both the hot and cold supply ducts are routed parallel to each other through the building and branch out to serve multiple zones within the area served by the unit.

Abbildung 3: Zweikanaliges System mit konstantem Luftvolumen

Jede Zone ist mit einer Doppelkanal-Mischbox ausgestattet, die über Warm- und Kaltkanal-Einlassanschlüsse verfügt, die jeweils mit einer motorbetriebenen Klappe und einem Einlassluftstromsensor ausgestattet sind. Die Zweikanal-Mischbox verfügt über einen Einzelkanalauslass, durch den der Zone Luft zugeführt wird. Die Temperatur der der Zone zugeführten Luft wird durch Modulation der Warm- und Kaltluftströme am Doppelkanal-Mischkasten nach Bedarf gesteuert, um den Sollwert des Zonenthermostats aufrechtzuerhalten. Bei CAV-Zweikanal-Mischkästen bleibt der gesamte Zuluftstrom zur Zone konstant.

Typischerweise wird die Lufttemperatur der Kaltdeckluft vom CAV-Klimagerät auf etwa 85 °F gehalten, so dass bei Bedarf eine Kühlung verfügbar ist, wenn die Temperaturzonen dies erfordern. Die Warmdecktemperatur der CAV-Einheit wird auf etwa 55 °F gehalten, so dass bei Bedarf eine Heizung verfügbar ist, wenn die Temperaturzonen dies erfordern. Die Heizschlange in einem Zweikanal-Lüftungsgerät kann Warmwasser, Dampf oder Strom sein. Die Kühlschlange besteht normalerweise aus gekühltem Wasser. Zweikanal-Lüftungsgeräte verwenden selten, wenn überhaupt, eine DX-Kältemittel-Kühlschlange.

Zweikanalige CAV-Systeme sind aufgrund der hohen Anschaffungskosten im Allgemeinen nicht für gewerbliche Gebäude geeignet. Daher werden wir auf Doppelkanalsysteme nicht näher eingehen. Doppelkanal-CAV-Systeme wurden vor Jahren hauptsächlich für die Versorgung von Laborbereichen innerhalb von Gebäuden entwickelt. Daher ist es für den HV-AC-Systemdesigner erforderlich, diesen Systemtyp zu verstehen, wenn ein Projekt die Renovierung eines Gebäudes mit einem Zweikanal-CAV-System umfasst. Heutzutage stehen jedoch mehr moderne HVAC-Systeme zur Versorgung von Laborbereichen zur Verfügung, die niedrigere Anschaffungs- und Betriebskosten haben als CAV-Systeme mit zwei Kanälen. Daher ist es unwahrscheinlich, dass ein neues Gebäude ein Zweikanal-CAV-System erfordert.


Mehrzonen

Multizone CAV systems are similar to dual-duct CAV systems in that there is a hot deck and a cold deck within the air handling unit (Fig. 4). The difference is that the hot and cold airstreams for each zone are mixed at the air handling unit. There is a hot and cold air motor-operated damper mounted on the discharge of the air handling unit for each zone; that is, if the unit is a five-zone unit, there will be five hot deck motor-operated dampers and five cold deck motor-operated dampers mounted on the discharge of the unit. There is a single duct connection on the combined outlet of each hot and cold damper serving each zone through which air is supplied to the zone. The temperature of the air supplied to each zone is controlled by modulating the hot and cold airflows at the air handling unit as required to maintain the setpoint of the zone thermostat. For CAV multizone systems, the total supply airflow to each zone remains constant. The hot and cold deck temperatures for multizone CAV systems are similar to the deck temperatures for dual-duct CAV systems.

Abbildung 4: Mehrzonen-CAV-System

Mehrzonen-CAV-Systeme werden in Gewerbegebäuden nicht häufig eingesetzt, da die verfügbaren VAV-Optionen in der Regel niedrigere Anschaffungs- und Betriebskosten haben. Außerdem ist die Anzahl der Zonen, die von einem Mehrzonengerät abgedeckt werden können, durch den physischen Platz begrenzt, der für die Installation der motorbetriebenen Heiß- und Kaltklappen für jede Zone am Auslass des Lüftungsgeräts zur Verfügung steht. Daher können Mehrzoneneinheiten nicht mehr als etwa acht Zonen bedienen. Die Anzahl der Zonen, die von einem VAV-System versorgt werden können, ist nicht durch die Ausrüstung begrenzt, sondern wird durch die Bedürfnisse der versorgten Gebiete bestimmt.

Quellenbuch für HVAC-Design - W. Larsen Angel, PE, LEED AP, ist Direktor des MEP-Beratungsunternehmens Green Building Energy Engineers. Er ist seit mehr als 30 Jahren in der MEP-Beratungstechnikbranche tätig. Herr Angel hat zur Entwicklung von Designstandards beigetragen und sucht weiterhin nach neuen Wegen, den Designprozess für HVAC-Systeme zu optimieren.

[dvfaqtopic title=”FREQUENTLY ASKED QUESTIONS” topicid=”18898″ skin=”custom” searchbox=”no” switcher=”yes” paginate=”” order=”ASC” orderby=”date”]